- Approvals/certifications Certified to EN54 Parts 11by the LPCB and 13 by the BSI
- Supply/operating voltage 4.5-30Vdc
- Product dimensions (mm) 87 W x 88 H x D 62mm (includes back box)
- Construction & finish Red ABS
- IP Rating IP42
- Properties – Supplied with a 470Ω & 680Ω resistor (value selected by wiring connection)
- Operating conditions/temperature -30ºC to 70ºC.
- Third-party certified to EN54-3 (Sounders) and EN54-23 (VADs).
- Provides ‘W-2.75-9’ rated light distribution when wall mounted (min. 0.4 lux over a 2.75 x 9m cuboid area). Also rated as W-4-4 VAD.
- Impressive 100dB(A) sound output @ 1m.
- Includes 31 selectable primary tones and an optional secondary tone.
- Two volume levels (high and low)
- Three selectable VAD flash rates (0.5Hz, 1Hz, OFF)
- Alarm Current at 30Vdc = 12.2mA (0.5Hz) or 19.5mA (1Hz)
- Alarm Current at 18Vdc = 14.5mA (0.5Hz) or 25mA (1Hz)
- IP55C rated (weatherproof).
- Manufactured in the UK by C-TEC.
- Manual callpoint with resettable element operated by plastic key (included).
- Warning flag and LED confirmation of activation.
- Selectable resistance.
- A high-quality red manual call point for use with C-TEC’s XFP & ZFP ‘CAST’ protocol Addressable Fire Panels.
- LPCB certified to EN54 Parts 11 & 17 and Kiwa Telefication certified to EN54-13.
- Surface or flush mountable.
- Onboard short-circuit loop isolator.
- Smooth-action resettable element mimics the feel of breaking glass.
- Supplied with reset/backbox removal key and ‘Not in Use’ label.
- Red LED ‘alarm ring’ illuminates call point face upon activation.
- The photoluminescent operating window remains visible for up to 5 minutes.
- 5mA typical alarm current (370µA typical quiescent @ 22-40V DC.
- IP42 rated (IP67 rated version also available, order code CA47067)
- Yellow, green, blue, and white versions also available.
- Addressable manual alarm button Enea;
- Operating temperature -30°C /+70°C
- Suitable for outdoor conditions IP67.
- Unique ‘Plug & Play’ installation concept
- Analogue addressable communications
- Fully compliant with EN54 and Part 11 of the Federal Code of Regulation Rules
- Integral LED
- Operates on 240VDS
- 100db @ 1 meter.
- Tri colour LED offering red, green and amber colour
- Rotary decade address switches 0 – 159
- Pure white colour to complement modern buildings
- 100% mechanical and electrical backwards compatibility
- New base design to complement the detector
- Fully compatible with C-TEC’s XFP & ZFP XP95/Discovery Addressable Fire Panels.
- Uses a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm.
- Responds well to fast-burning, flaming fires.
- Designed to operate in a variety of environments.
- Red LED illuminates when the detector is in alarm.
- Certified to EN54-7 by the LPCB.
- Requires a 45681-210APO standard base or 45681-242APO low power relay base.
- ‘Xpert’ card addressed for speedy installation.
- Low profile, two inches including the base
- Simple and reliable addressing without mechanical switches
- Automatic compensation for sensor contamination
- Built-in fire test feature
- Vandal resistance locking features
- Field cleanable

Inim ED100 Optical Smoke Detector
SKU: N/AED100
Optical smoke detector
The ED100 optical smoke detector is based on the Tyndall effect (diffusion of light) and provides firstrate early warning in the event of fire.
It offers wide-spectrum detection of smoke particles generated by the majority of fires. The newly designed optical chamber with sealed upper-part and 500 μm holes diameter mesh insect screen ensure high immunity to false alarms.
The sensitivity can be configured to suit a wide range of applications (sensitivity configurable as: 0.08dB/m; 0.10dB/m; 0.12dB/m; 0.15dB/m).

C-Tec Manual Resettable Call Point
SKU: N/AC-Tec Manual Resettable Call Point

Conventional Weatherproof Hi-Output W-2.75-9 Wall VAD c/w 100dB(A) Sounder beacon
SKU: N/AConventional Weatherproof Hi-Output W-2.75-9 Wall VAD c/w 100dB(A) Sounder beacon

Inim IC0020 Manual Call Point
SKU: N/AIC0020

Conventional Visual Sounder alarm indicator
SKU: N/AConventional Visual Sounder alarm indicator
Acoustic and visual alarm indicator approved according new EN54-23 standard, IP65 protection rated (deep base version only), Operating voltage from 17 to 60 Vdc, mounting base included.
Selectable tone among 32 available by means of DIP SWITCH, flashing frequency selectable at 0,5Hz / 1Hz (by means of DIP SWITCH), 2 selectable sound level

C-TEC CA470 Cast Addressable Manual Call Point
SKU: N/AC-Tec CA470 CAST Addressable Manual Call Point Features

EC0011E Manual callpoint (IP67)
SKU: N/AEC0011E Manual callpoint for outdoor installation (IP67)

Morley IAS MI-MCP-Glass Addressable Glass Manual Call Point
SKU: N/AMorley IAS MI-MCP-Glass Addressable Glass Manual Call Point

Morley Honeywell Sounder and Flasher
SKU: N/AMorley Honeywell Sounder and Flasher

ES2000 Addressable wall mount audible/visual-audible alarm indicator
SKU: N/AES2000 Addressable wall mount audible/visual-audible alarm indicator
Wall mount addressable audible/visual-audible alarm indicator, IP65 protection rating.
Volume, flash intensity, and sound sequences can be selected via the control panel (and diversified in accordance with the situation) from the 14 tones and 16 voice messages available in 8 different languages on-board the device (only for versions with the voice function).*
For models with the voice function, it is also possible to customize tones/voice messages by means of the EITK2000.
The device is powered via the loop but is equipped with terminals for optional separate power input.

C-TEC ADDRESSABLE CX VOICE SOUNDER & VAD BEACON – RED – EN54-3 & EN54-23 BF453A/CX/SR
SKU: N/AC-TEC ADDRESSABLE CX VOICE SOUNDER & VAD BEACON – RED – EN54-3 & EN54-23
The C-Tec BF453A/CX/SR is an addressable combined voice sounder & VAD beacon in red ideal for use on the XFP & ZFP Discovery protocol fire alarm systems.

MORLEY HEAT DETECTOR FIXED TEMPERATURE ADDRESSABLE – MI-FHSE-S2
SKU: N/AMORLEY HEAT DETECTOR FIXED TEMPERATURE ADDRESSABLE – MI-FHSE-S2

Inim ED200 Optical Heat detector
SKU: N/AThe ED200 heat detector can be configured in the following modes: A1R mode (fixed threshold at 58°C with thermovelocimetric detection); B mode (fixed threshold at 72°C); A2S mode (fixed threshold at 58°C); BR mode (fixed threshold at 72°C with thermovelocimetric detection).
As a result of high flexibility, this detector is useful in places where the environment is dusty or smoky and the risk of false alarms is high.

Apollo XP95 Ionisation Smoke Detector
SKU: N/AApollo XP95 Ionisation Smoke Detector

Honeywell Addressable Photoelectric Smoke Detector
SKU: N/A- Approvals/certifications Certified to EN54 Parts 11by the LPCB and 13 by the BSI
- Supply/operating voltage 4.5-30Vdc
- Product dimensions (mm) 87 W x 88 H x D 62mm (includes back box)
- Construction & finish Red ABS
- IP Rating IP42
- Properties – Supplied with a 470Ω & 680Ω resistor (value selected by wiring connection)
- Operating conditions/temperature -30ºC to 70ºC.
- Third-party certified to EN54-3 (Sounders) and EN54-23 (VADs).
- Provides ‘W-2.75-9’ rated light distribution when wall mounted (min. 0.4 lux over a 2.75 x 9m cuboid area). Also rated as W-4-4 VAD.
- Impressive 100dB(A) sound output @ 1m.
- Includes 31 selectable primary tones and an optional secondary tone.
- Two volume levels (high and low)
- Three selectable VAD flash rates (0.5Hz, 1Hz, OFF)
- Alarm Current at 30Vdc = 12.2mA (0.5Hz) or 19.5mA (1Hz)
- Alarm Current at 18Vdc = 14.5mA (0.5Hz) or 25mA (1Hz)
- IP55C rated (weatherproof).
- Manufactured in the UK by C-TEC.
- Manual callpoint with resettable element operated by plastic key (included).
- Warning flag and LED confirmation of activation.
- Selectable resistance.
- A high-quality red manual call point for use with C-TEC’s XFP & ZFP ‘CAST’ protocol Addressable Fire Panels.
- LPCB certified to EN54 Parts 11 & 17 and Kiwa Telefication certified to EN54-13.
- Surface or flush mountable.
- Onboard short-circuit loop isolator.
- Smooth-action resettable element mimics the feel of breaking glass.
- Supplied with reset/backbox removal key and ‘Not in Use’ label.
- Red LED ‘alarm ring’ illuminates call point face upon activation.
- The photoluminescent operating window remains visible for up to 5 minutes.
- 5mA typical alarm current (370µA typical quiescent @ 22-40V DC.
- IP42 rated (IP67 rated version also available, order code CA47067)
- Yellow, green, blue, and white versions also available.
- Addressable manual alarm button Enea;
- Operating temperature -30°C /+70°C
- Suitable for outdoor conditions IP67.
- Unique ‘Plug & Play’ installation concept
- Analogue addressable communications
- Fully compliant with EN54 and Part 11 of the Federal Code of Regulation Rules
- Integral LED
- Operates on 240VDS
- 100db @ 1 meter.
- Tri colour LED offering red, green and amber colour
- Rotary decade address switches 0 – 159
- Pure white colour to complement modern buildings
- 100% mechanical and electrical backwards compatibility
- New base design to complement the detector
- Fully compatible with C-TEC’s XFP & ZFP XP95/Discovery Addressable Fire Panels.
- Uses a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm.
- Responds well to fast-burning, flaming fires.
- Designed to operate in a variety of environments.
- Red LED illuminates when the detector is in alarm.
- Certified to EN54-7 by the LPCB.
- Requires a 45681-210APO standard base or 45681-242APO low power relay base.
- ‘Xpert’ card addressed for speedy installation.
- Low profile, two inches including the base
- Simple and reliable addressing without mechanical switches
- Automatic compensation for sensor contamination
- Built-in fire test feature
- Vandal resistance locking features
- Field cleanable

Inim ED100 Optical Smoke Detector
ED100
Optical smoke detector
The ED100 optical smoke detector is based on the Tyndall effect (diffusion of light) and provides firstrate early warning in the event of fire.
It offers wide-spectrum detection of smoke particles generated by the majority of fires. The newly designed optical chamber with sealed upper-part and 500 μm holes diameter mesh insect screen ensure high immunity to false alarms.
The sensitivity can be configured to suit a wide range of applications (sensitivity configurable as: 0.08dB/m; 0.10dB/m; 0.12dB/m; 0.15dB/m).

C-Tec Manual Resettable Call Point
C-Tec Manual Resettable Call Point

Conventional Weatherproof Hi-Output W-2.75-9 Wall VAD c/w 100dB(A) Sounder beacon
Conventional Weatherproof Hi-Output W-2.75-9 Wall VAD c/w 100dB(A) Sounder beacon

Inim IC0020 Manual Call Point
IC0020

Conventional Visual Sounder alarm indicator
Conventional Visual Sounder alarm indicator
Acoustic and visual alarm indicator approved according new EN54-23 standard, IP65 protection rated (deep base version only), Operating voltage from 17 to 60 Vdc, mounting base included.
Selectable tone among 32 available by means of DIP SWITCH, flashing frequency selectable at 0,5Hz / 1Hz (by means of DIP SWITCH), 2 selectable sound level

C-TEC CA470 Cast Addressable Manual Call Point
C-Tec CA470 CAST Addressable Manual Call Point Features

EC0011E Manual callpoint (IP67)
EC0011E Manual callpoint for outdoor installation (IP67)

Morley IAS MI-MCP-Glass Addressable Glass Manual Call Point
Morley IAS MI-MCP-Glass Addressable Glass Manual Call Point

Morley Honeywell Sounder and Flasher
Morley Honeywell Sounder and Flasher

ES2000 Addressable wall mount audible/visual-audible alarm indicator
ES2000 Addressable wall mount audible/visual-audible alarm indicator
Wall mount addressable audible/visual-audible alarm indicator, IP65 protection rating.
Volume, flash intensity, and sound sequences can be selected via the control panel (and diversified in accordance with the situation) from the 14 tones and 16 voice messages available in 8 different languages on-board the device (only for versions with the voice function).*
For models with the voice function, it is also possible to customize tones/voice messages by means of the EITK2000.
The device is powered via the loop but is equipped with terminals for optional separate power input.

C-TEC ADDRESSABLE CX VOICE SOUNDER & VAD BEACON – RED – EN54-3 & EN54-23 BF453A/CX/SR
C-TEC ADDRESSABLE CX VOICE SOUNDER & VAD BEACON – RED – EN54-3 & EN54-23
The C-Tec BF453A/CX/SR is an addressable combined voice sounder & VAD beacon in red ideal for use on the XFP & ZFP Discovery protocol fire alarm systems.

MORLEY HEAT DETECTOR FIXED TEMPERATURE ADDRESSABLE – MI-FHSE-S2
MORLEY HEAT DETECTOR FIXED TEMPERATURE ADDRESSABLE – MI-FHSE-S2

Inim ED200 Optical Heat detector
The ED200 heat detector can be configured in the following modes: A1R mode (fixed threshold at 58°C with thermovelocimetric detection); B mode (fixed threshold at 72°C); A2S mode (fixed threshold at 58°C); BR mode (fixed threshold at 72°C with thermovelocimetric detection).
As a result of high flexibility, this detector is useful in places where the environment is dusty or smoky and the risk of false alarms is high.

Apollo XP95 Ionisation Smoke Detector
Apollo XP95 Ionisation Smoke Detector

Honeywell Addressable Photoelectric Smoke Detector
- Approvals/certifications Certified to EN54 Parts 11by the LPCB and 13 by the BSI
- Supply/operating voltage 4.5-30Vdc
- Product dimensions (mm) 87 W x 88 H x D 62mm (includes back box)
- Construction & finish Red ABS
- IP Rating IP42
- Properties – Supplied with a 470Ω & 680Ω resistor (value selected by wiring connection)
- Operating conditions/temperature -30ºC to 70ºC.
- Third-party certified to EN54-3 (Sounders) and EN54-23 (VADs).
- Provides ‘W-2.75-9’ rated light distribution when wall mounted (min. 0.4 lux over a 2.75 x 9m cuboid area). Also rated as W-4-4 VAD.
- Impressive 100dB(A) sound output @ 1m.
- Includes 31 selectable primary tones and an optional secondary tone.
- Two volume levels (high and low)
- Three selectable VAD flash rates (0.5Hz, 1Hz, OFF)
- Alarm Current at 30Vdc = 12.2mA (0.5Hz) or 19.5mA (1Hz)
- Alarm Current at 18Vdc = 14.5mA (0.5Hz) or 25mA (1Hz)
- IP55C rated (weatherproof).
- Manufactured in the UK by C-TEC.
- Manual callpoint with resettable element operated by plastic key (included).
- Warning flag and LED confirmation of activation.
- Selectable resistance.
- A high-quality red manual call point for use with C-TEC’s XFP & ZFP ‘CAST’ protocol Addressable Fire Panels.
- LPCB certified to EN54 Parts 11 & 17 and Kiwa Telefication certified to EN54-13.
- Surface or flush mountable.
- Onboard short-circuit loop isolator.
- Smooth-action resettable element mimics the feel of breaking glass.
- Supplied with reset/backbox removal key and ‘Not in Use’ label.
- Red LED ‘alarm ring’ illuminates call point face upon activation.
- The photoluminescent operating window remains visible for up to 5 minutes.
- 5mA typical alarm current (370µA typical quiescent @ 22-40V DC.
- IP42 rated (IP67 rated version also available, order code CA47067)
- Yellow, green, blue, and white versions also available.
- Addressable manual alarm button Enea;
- Operating temperature -30°C /+70°C
- Suitable for outdoor conditions IP67.
- Unique ‘Plug & Play’ installation concept
- Analogue addressable communications
- Fully compliant with EN54 and Part 11 of the Federal Code of Regulation Rules
- Integral LED
- Operates on 240VDS
- 100db @ 1 meter.
- Tri colour LED offering red, green and amber colour
- Rotary decade address switches 0 – 159
- Pure white colour to complement modern buildings
- 100% mechanical and electrical backwards compatibility
- New base design to complement the detector
- Fully compatible with C-TEC’s XFP & ZFP XP95/Discovery Addressable Fire Panels.
- Uses a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm.
- Responds well to fast-burning, flaming fires.
- Designed to operate in a variety of environments.
- Red LED illuminates when the detector is in alarm.
- Certified to EN54-7 by the LPCB.
- Requires a 45681-210APO standard base or 45681-242APO low power relay base.
- ‘Xpert’ card addressed for speedy installation.
- Low profile, two inches including the base
- Simple and reliable addressing without mechanical switches
- Automatic compensation for sensor contamination
- Built-in fire test feature
- Vandal resistance locking features
- Field cleanable

Inim ED100 Optical Smoke Detector
ED100
Optical smoke detector
The ED100 optical smoke detector is based on the Tyndall effect (diffusion of light) and provides firstrate early warning in the event of fire.
It offers wide-spectrum detection of smoke particles generated by the majority of fires. The newly designed optical chamber with sealed upper-part and 500 μm holes diameter mesh insect screen ensure high immunity to false alarms.
The sensitivity can be configured to suit a wide range of applications (sensitivity configurable as: 0.08dB/m; 0.10dB/m; 0.12dB/m; 0.15dB/m).

C-Tec Manual Resettable Call Point
C-Tec Manual Resettable Call Point

Conventional Weatherproof Hi-Output W-2.75-9 Wall VAD c/w 100dB(A) Sounder beacon
Conventional Weatherproof Hi-Output W-2.75-9 Wall VAD c/w 100dB(A) Sounder beacon

Inim IC0020 Manual Call Point
IC0020

Conventional Visual Sounder alarm indicator
Conventional Visual Sounder alarm indicator
Acoustic and visual alarm indicator approved according new EN54-23 standard, IP65 protection rated (deep base version only), Operating voltage from 17 to 60 Vdc, mounting base included.
Selectable tone among 32 available by means of DIP SWITCH, flashing frequency selectable at 0,5Hz / 1Hz (by means of DIP SWITCH), 2 selectable sound level

C-TEC CA470 Cast Addressable Manual Call Point
C-Tec CA470 CAST Addressable Manual Call Point Features

EC0011E Manual callpoint (IP67)
EC0011E Manual callpoint for outdoor installation (IP67)

Morley IAS MI-MCP-Glass Addressable Glass Manual Call Point
Morley IAS MI-MCP-Glass Addressable Glass Manual Call Point

Morley Honeywell Sounder and Flasher
Morley Honeywell Sounder and Flasher

ES2000 Addressable wall mount audible/visual-audible alarm indicator
ES2000 Addressable wall mount audible/visual-audible alarm indicator
Wall mount addressable audible/visual-audible alarm indicator, IP65 protection rating.
Volume, flash intensity, and sound sequences can be selected via the control panel (and diversified in accordance with the situation) from the 14 tones and 16 voice messages available in 8 different languages on-board the device (only for versions with the voice function).*
For models with the voice function, it is also possible to customize tones/voice messages by means of the EITK2000.
The device is powered via the loop but is equipped with terminals for optional separate power input.

C-TEC ADDRESSABLE CX VOICE SOUNDER & VAD BEACON – RED – EN54-3 & EN54-23 BF453A/CX/SR
C-TEC ADDRESSABLE CX VOICE SOUNDER & VAD BEACON – RED – EN54-3 & EN54-23
The C-Tec BF453A/CX/SR is an addressable combined voice sounder & VAD beacon in red ideal for use on the XFP & ZFP Discovery protocol fire alarm systems.

MORLEY HEAT DETECTOR FIXED TEMPERATURE ADDRESSABLE – MI-FHSE-S2
MORLEY HEAT DETECTOR FIXED TEMPERATURE ADDRESSABLE – MI-FHSE-S2

Inim ED200 Optical Heat detector
The ED200 heat detector can be configured in the following modes: A1R mode (fixed threshold at 58°C with thermovelocimetric detection); B mode (fixed threshold at 72°C); A2S mode (fixed threshold at 58°C); BR mode (fixed threshold at 72°C with thermovelocimetric detection).
As a result of high flexibility, this detector is useful in places where the environment is dusty or smoky and the risk of false alarms is high.

Apollo XP95 Ionisation Smoke Detector
Apollo XP95 Ionisation Smoke Detector

Honeywell Addressable Photoelectric Smoke Detector
- Approvals/certifications Certified to EN54 Parts 11by the LPCB and 13 by the BSI
- Supply/operating voltage 4.5-30Vdc
- Product dimensions (mm) 87 W x 88 H x D 62mm (includes back box)
- Construction & finish Red ABS
- IP Rating IP42
- Properties – Supplied with a 470Ω & 680Ω resistor (value selected by wiring connection)
- Operating conditions/temperature -30ºC to 70ºC.
- Third-party certified to EN54-3 (Sounders) and EN54-23 (VADs).
- Provides ‘W-2.75-9’ rated light distribution when wall mounted (min. 0.4 lux over a 2.75 x 9m cuboid area). Also rated as W-4-4 VAD.
- Impressive 100dB(A) sound output @ 1m.
- Includes 31 selectable primary tones and an optional secondary tone.
- Two volume levels (high and low)
- Three selectable VAD flash rates (0.5Hz, 1Hz, OFF)
- Alarm Current at 30Vdc = 12.2mA (0.5Hz) or 19.5mA (1Hz)
- Alarm Current at 18Vdc = 14.5mA (0.5Hz) or 25mA (1Hz)
- IP55C rated (weatherproof).
- Manufactured in the UK by C-TEC.
- Manual callpoint with resettable element operated by plastic key (included).
- Warning flag and LED confirmation of activation.
- Selectable resistance.
- A high-quality red manual call point for use with C-TEC’s XFP & ZFP ‘CAST’ protocol Addressable Fire Panels.
- LPCB certified to EN54 Parts 11 & 17 and Kiwa Telefication certified to EN54-13.
- Surface or flush mountable.
- Onboard short-circuit loop isolator.
- Smooth-action resettable element mimics the feel of breaking glass.
- Supplied with reset/backbox removal key and ‘Not in Use’ label.
- Red LED ‘alarm ring’ illuminates call point face upon activation.
- The photoluminescent operating window remains visible for up to 5 minutes.
- 5mA typical alarm current (370µA typical quiescent @ 22-40V DC.
- IP42 rated (IP67 rated version also available, order code CA47067)
- Yellow, green, blue, and white versions also available.
- Addressable manual alarm button Enea;
- Operating temperature -30°C /+70°C
- Suitable for outdoor conditions IP67.
- Unique ‘Plug & Play’ installation concept
- Analogue addressable communications
- Fully compliant with EN54 and Part 11 of the Federal Code of Regulation Rules
- Integral LED
- Operates on 240VDS
- 100db @ 1 meter.
- Tri colour LED offering red, green and amber colour
- Rotary decade address switches 0 – 159
- Pure white colour to complement modern buildings
- 100% mechanical and electrical backwards compatibility
- New base design to complement the detector
- Fully compatible with C-TEC’s XFP & ZFP XP95/Discovery Addressable Fire Panels.
- Uses a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm.
- Responds well to fast-burning, flaming fires.
- Designed to operate in a variety of environments.
- Red LED illuminates when the detector is in alarm.
- Certified to EN54-7 by the LPCB.
- Requires a 45681-210APO standard base or 45681-242APO low power relay base.
- ‘Xpert’ card addressed for speedy installation.
- Low profile, two inches including the base
- Simple and reliable addressing without mechanical switches
- Automatic compensation for sensor contamination
- Built-in fire test feature
- Vandal resistance locking features
- Field cleanable

Inim ED100 Optical Smoke Detector
ED100
Optical smoke detector
The ED100 optical smoke detector is based on the Tyndall effect (diffusion of light) and provides firstrate early warning in the event of fire.
It offers wide-spectrum detection of smoke particles generated by the majority of fires. The newly designed optical chamber with sealed upper-part and 500 μm holes diameter mesh insect screen ensure high immunity to false alarms.
The sensitivity can be configured to suit a wide range of applications (sensitivity configurable as: 0.08dB/m; 0.10dB/m; 0.12dB/m; 0.15dB/m).

C-Tec Manual Resettable Call Point
C-Tec Manual Resettable Call Point

Conventional Weatherproof Hi-Output W-2.75-9 Wall VAD c/w 100dB(A) Sounder beacon
Conventional Weatherproof Hi-Output W-2.75-9 Wall VAD c/w 100dB(A) Sounder beacon

Inim IC0020 Manual Call Point
IC0020

Conventional Visual Sounder alarm indicator
Conventional Visual Sounder alarm indicator
Acoustic and visual alarm indicator approved according new EN54-23 standard, IP65 protection rated (deep base version only), Operating voltage from 17 to 60 Vdc, mounting base included.
Selectable tone among 32 available by means of DIP SWITCH, flashing frequency selectable at 0,5Hz / 1Hz (by means of DIP SWITCH), 2 selectable sound level

C-TEC CA470 Cast Addressable Manual Call Point
C-Tec CA470 CAST Addressable Manual Call Point Features

EC0011E Manual callpoint (IP67)
EC0011E Manual callpoint for outdoor installation (IP67)

Morley IAS MI-MCP-Glass Addressable Glass Manual Call Point
Morley IAS MI-MCP-Glass Addressable Glass Manual Call Point

Morley Honeywell Sounder and Flasher
Morley Honeywell Sounder and Flasher

ES2000 Addressable wall mount audible/visual-audible alarm indicator
ES2000 Addressable wall mount audible/visual-audible alarm indicator
Wall mount addressable audible/visual-audible alarm indicator, IP65 protection rating.
Volume, flash intensity, and sound sequences can be selected via the control panel (and diversified in accordance with the situation) from the 14 tones and 16 voice messages available in 8 different languages on-board the device (only for versions with the voice function).*
For models with the voice function, it is also possible to customize tones/voice messages by means of the EITK2000.
The device is powered via the loop but is equipped with terminals for optional separate power input.

C-TEC ADDRESSABLE CX VOICE SOUNDER & VAD BEACON – RED – EN54-3 & EN54-23 BF453A/CX/SR
C-TEC ADDRESSABLE CX VOICE SOUNDER & VAD BEACON – RED – EN54-3 & EN54-23
The C-Tec BF453A/CX/SR is an addressable combined voice sounder & VAD beacon in red ideal for use on the XFP & ZFP Discovery protocol fire alarm systems.

MORLEY HEAT DETECTOR FIXED TEMPERATURE ADDRESSABLE – MI-FHSE-S2
MORLEY HEAT DETECTOR FIXED TEMPERATURE ADDRESSABLE – MI-FHSE-S2

Inim ED200 Optical Heat detector
The ED200 heat detector can be configured in the following modes: A1R mode (fixed threshold at 58°C with thermovelocimetric detection); B mode (fixed threshold at 72°C); A2S mode (fixed threshold at 58°C); BR mode (fixed threshold at 72°C with thermovelocimetric detection).
As a result of high flexibility, this detector is useful in places where the environment is dusty or smoky and the risk of false alarms is high.

Apollo XP95 Ionisation Smoke Detector
Apollo XP95 Ionisation Smoke Detector