C-Tec Addressable Heat Detector

Brand:C-TEC

Availability:In Stock!

C-Tec Addressable Heat Detector
  • A high-quality programmable heat detector for use with C-TEC’s XFP & ZFP ‘CAST’ protocol Addressable Fire Panels.
  • LPCB certified to EN54-5 & 17 and Kiwa Telefication certified to EN54-13.
  • Can be programmed to operate as a Class A1R (rate of rise), Class A2 (64ºC fixed temperature) or Class B (76ºC fixed temperature) heat detector. The default setting is A2.
  • Onboard short circuit loop isolator.
  • Includes two 8mm x 2mm ultra-bright red LED indicating strips.
  • Different sensitivities can be selected for different times of the day (day/night, building occupied/unoccupied etc).
  • 5mA typical alarm current (370uA typical quiescent) @ 22-40V DC.
  • Programmable multi-function status LED.
  • Compatible with C-TEC’s CA408 CAST base c/w integrated locking mechanism & ID tag.
Compare

KSh6,000.00 Excl. VAT

Please confirm product availability before placing an order.
Prices are subject to change without notice.
Delivery at a fee. Same Day Delivery within Nairobi.
Secure Payment Options
Mpesa Payment Visa Payment Mastercard Payment

Order on Whatsapp

Compare

Description

C-Tec Addressable Heat Detector

The C-Tec CA402 is a CAST protocol programmable analogue addressable heat smoke detector for use on the C-Tec CAST protocol range of fire alarm system equipment.

Technical Specifications

Approvals/certifications LPCB certified to EN54-5 & 17 and Kiwa Telefication certified to EN54-13.
Compatibility Compatible with C-TEC’s XFP/ZFP CAST Protocol Addressable Fire Panels.
Type Class A1R, Class A2 or Class B Heat (Programmable).
Application/operation Generates an alarm when a specific temperature is reached (Modes 1, 2 & 3). In Mode 1 also generates an alarm when a sudden rise in temp is detected.
Sensitivity Mode 1 (A1R): Rate of Rise and 56ºC fixed; Mode 2 (A2): 62ºC fixed; Mode 3 (B): 74ºC fixed. Selectable at the panel.
Supply wiring 2-wire, polarity sensitive.
Supply/operating voltage 22 to 40V DC.
Quiescent current 370µA typical @ 22 to 40V DC.
Alarm current 5mA typical (LEDs illuminated) @ 22 to 40V DC.
Indicators 2 LED indicator strips emitting red light when in alarm offering 360º visibility. Optional remote LED.
Connections Via CA408 base: 1 +Ve IN (analogue swich); 2 +Ve OUT (analogue switch); 3 Remote LED +Ve; 4 0V; 5 0V; 6 Screen; 7 Screen.
Product dimensions (mm) 102.2mm diameter x 37mm deep (detector only); 102.2mm diameter x 57.5mm deep (detector in base).
Construction & finish White polycarbonate casing rated to UL94 V-2 with nylon parts.
IP Rating IP42.
Weight 99g (not in base); 154g (in base).
Operating conditions/temperature -20ºC to +85ºC.
Notes Requires a CA408 CAST base. CA408R relay base also available.